Oapt, Pv color change – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 175
Publication 900-UM007D-EN-E - January 2011
Parameter Adjustments & Application Considerations
4-39
EXAMPLE
Operating Procedure: With No Password Set
Figure 4.69
1. Press the O and M keys simultaneously for at least the time
configured in the Operation/Adjustment Protect parameter to move
from the Operation function group to the Protect function group.
When a password is not configured, the Operation/Adjustment Protect
parameter will be displayed.
Figure 4.70
Communications Operation Command to Move to the Protect function group
The Write Variable operation command can be used via communications to
write the password to the Move to Protect function group parameter. When
the correct password is written, the display will change to the Operation/
Adjustment Protect parameter and writing the parameters in the Protect
function group will be enabled.
Note: If the Write Variable operation command is used to write the wrong
password to the Move to Protect function group parameter after the
correct parameter has been written, the Move to Protect function group
parameter will be displayed and any Write Variable operation
commands to write parameters in the protect function group will result
in operation errors.
Note: If a password is not configured or if it is configured to 0, the display will
change to the Operation/Adjustment Protect parameter and writing the
parameters in the Protect function group will be enabled immediately.
PV Color Change
PV Color Change Function
Use the PV color change function to configure the color of the PV display
(No. 1 display).
C
25
100
PV/SP
oapt
0
Operation/adjustment protect