Bulletin 280G/281G Programmable Parameters

3-25

Overload Class

This parameter allows the
installer to select the overload
class

1= Overload Class 10
2= Overload Class 15
3= Overload Class 20

Parameter Number

107

Access Rule

GET/SET

Data Type

USINT

Group

Starter Setup

Units

xx.x Amps

Minimum Value

1

Maximum Value

3

Default Value

1

OL Reset Level

This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared

Parameter Number

108

Access Rule

GET/SET

Data Type

USINT

Group

Starter Setup

Units

% FLA

Minimum Value

0

Maximum Value

100

Default Value

75