Specifications

A-11

ArmorConnect™ Three-Phase Power Media

Table 1.A Patchcords

The cat. no. is incomplete as shown. For desired length, replace the symbol with: 05 —0.5 m (1.62 ft), 1—1 m (3.3 ft), 015—1.5 m (4.9 ft), 2—2 m (6.5 ft),
025—2.5 m (8.1 ft), 3—3 m (9.8 ft), 4—4 m (13.1 ft), 6—6 m (19.7 ft), 8—8 m (26.2 ft), 10—10 m (32.8 ft), 12—12 m (39.4 ft), or 14—14 m (45.9 ft).

Specifications

Pinout and Color Code

Approximate Dimensions

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes and are subject to change.

Pin

Count

Assembly

Rating

Cat. No.

0

0

4-pin

600V, 25 A

Straight Female

Straight Male

Right-Angle Female

Straight Male

Straight Female

Right-Angle Male

Right-Angle Female

Right-Angle Male

280-PWRM35A-M

280-PWRM35A-M

280-PWRM35A-M

280-PWRM35A-M

Mechanical

Coupling Nut

Black Anodized Aluminum or 316 Stainless Steel

Housing

Black PVC

Insert

Black PVC

Cable Diameter

0.775 in. +/- 0.12 in. (19.68 mm +/- 0.5 mm)

Electrical

Contacts

Copper Alloy with Gold over Nickel Plating

Cable

Black PVC, dual rated UL TC/Open Wiring and STOOW

Cable Rating

600V AC/DC

Assembly Rating

600V @ 25 A, Symmetrical Amps RMS Fault: 65 kA when

used with Class CC, T, or J type fuses

or 100 A circuit breaker

Environmental

Enclosure Type Rating

IP67, NEMA 4; IP69K 1200 psi washdown

Operating Temperature

UL Type TC 600V 90 °C Dry 75 °C Wet, Exposed Run (ER) or

MTW 600V 90 °C or STOOW 105 °C 600V -

CSA STOOW 600V FT2

Certifications

UL Listed (File No. E318496, Guide PVVA)

Standards Compliance

UL 2237

Face View Pinout

4-pin

Female

Male

Color Code

1 Black

3 Red

2 Green/Yellow Extended PIN

4 White

88.9 (3.50)

38.6

(1.52)

Female straight

(1.95 - 2.25)

(2.94)

(1.52)

74.7

49.5 - 57.1

38.6

Female 90 deg.

88.9 (3.50)

38.6
(1.52)

Male straight

(1.95 - 2.25)

(2.94)

(1.52)

74.7

49.5 - 57.1

38.6

Male 90 deg.

Example of a Patchcord