Clear fault, Fault codes – Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 186

9-2
Diagnostics
Clear Fault
You may clear a fault using the following methods:
•
Remotely via network communications
•
A remote reset will be attempted upon detection of a rising edge
(0 to 1 transition) of the “Fault Reset” bit in the various I/O
assemblies. A remote reset will also be attempted upon detection
of the rising edge of the “Fault Reset” parameter.
•
Locally via the “Reset” button on the LED Status indication
keypad.
Fault Codes
Table 9.1 provides a complete reference of the Fault LED indications
for Bulletin 280G/281G and 284G ArmorStart Distributed Motor
Controllers.
Table 9.1
Fault Indication
Blink Pattern
Fault Types
Bulletin 280G/281G
Bulletin 284G
1
Short Circuit
Short Circuit
2
Overload Trip
Overload Trip
3
Phase Loss
Phase Short
4
Reserved
Ground Fault
5
Reserved
Stall
6
Control Power
Control Power
7
I/O Fault
I/O Fault
8
Over Temperature
Over Temperature
9
Phase Imbalance
Over Current
10
DeviceNet™ Power Loss
DeviceNet™ Power Loss
11
Reserved
Internal Communications
12
Reserved
DC Bus Fault
13
EEPROM Fault
EEPROM Fault
14
Hardware Fault
Hardware Fault
15
Reserved
Restart Retries
16
Reserved
Misc. Fault