Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 126

4-46
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Figure 4.6
Anlg In 0…10V Lo
Sets the analog input level that corresponds to parameter 134 (Minimum Freq) if a
0…10V input is used by parameter 138 (Speed Reference)
Parameter Number
210
Related Parameter
121, 134, 138, 222
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1%
Minimum Value
0.0%
Maximum Value
100.0%
Default Value
0.0%
Stop drive before changing this parameter.
Anlg In 0…10V HI
Sets the analog input level that corresponds to parameter 135 (Maximum Freq) if a
0…10V input is used by parameter 138 (Speed Reference). Analog inversion can be
accomplished by setting this value smaller than parameter 210 (Anlg In 0…10V Lo).
Parameter Number
211
Related Parameter
121, 135, 138, 222, 223
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1%
Minimum Value
0.0%
Maximum Value
100.0%
Default Value
0.0%
Anlg In4…20MA LO
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
212
Anlg In4…20 mA HI
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number
213
0
Parameter 135
[Maximum Freq]
Parameter 134
[Minimum Freq]
Parameter 210
[Anlg In 0-10V Lo]
Parameter 211
[Anlg In 0-10V Hi]
0
Speed Reference
Stop drive before changing this parameter.