Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 265

Bulletin 284G CIP Information
C-15
Instance 4 is the Predefined Group 2 Connection Set Change of State/
Cyclic I/O Message Connection. The following Instance 4 attributes
are supported
Table C.37 Connection Object Instance 4 Attributes:
Attribute
ID
Access
Rule
Name
Data
Type
Value
1
Get
State
USINT
0 = non-existent
1 = configuring
3 = established
4 = timed out
2
Get
Instance Type
USINT
1 = I/O Connection
3
Get
Transport Class Trigger
USINT
0x00 (Cyclic,
unacknowledged)
0x03 (Cyclic,
acknowledged)
0x10 (COS,
unacknowledged)
0x13 (COS,
acknowledged)
4
Get
Produced Connection ID
UINT
01101xxxxxx
xxxxxx = node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx = node address
6
Get
Initial Comm Characteristics
USINT
0x02 (acknowledged)
0x0F (unacknowledged)
7
Get
Produced Connection Size
UINT
0…8
8
Get
Consumed Connection Size
UINT
0…8
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get
Watchdog Action
USINT
0 = transition to timed
out
1 = auto delete
2 = auto reset
13
Get
Produced Connection Path
Length
UINT
8
14
Get
Produced Connection Path
21 04 00 25 (assy inst)
00 30 03
15
Get
Consumed Connection Path
Length
UINT
8
16
Get/Set
Consumed Connection Path
21 04 00 25 (assy inst)
00 30 03