Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Var PWM Disable
Enables/disables a feature that varies the carrier frequency for the PWM output
waveform defined by Parameter 191 (PWM Frequency).
0 = Enabled
1 = Disabled
Disabling this feature when low frequency condition exists may result in IGBT stress
and nuisance tripping.
Parameter Number
224
Related Parameters
191
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Torque Perf Mode
Enables/disables sensorless vector control operation.
0 = V/Hz
1 = Sensrls Vect
Parameter Number
225
Related Parameters
184, 185, 186, 187, 227
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
1
Default Value
1
Motor NP FLA
Set to the motor nameplate full load amps.
Parameter Number
226
Related Parameters
227
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 A
Minimum Value
0.1
Maximum Value
Drive rated amps x 2
Default Value
Drive rated amps
Stop drive before changing this parameter.
Stop drive before changing this parameter.