Bulletin 280G/281G CIP Information
Control Supervisor Object -CLASS
CODE 0x0029
No class attributes are supported.
The following instance attributes are supported:
A single instance (instance 1) of the Control Supervisor Object will
be supported.
Table B.52 Control Supervisor Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Value
3
Get/Set
Run 1
BOOL
These Run outputs also map to DOP instances 1
and 2.
*4
Get/Set
Run 2
BOOL
7
Get
Running 1
BOOL
Status of RUN FWD contact
*8
Get
Running 2
BOOL
Status of RUN REV contact
9
Get
Ready
BOOL
Device not faulted
10
Get
Tripped
BOOL
Device faulted
12
Get/Set
Fault Reset
BOOL
0->1 = Trip Reset
100
Get/Set
Keypad Mode
BOOL
0=Maintained; 1=Momentary
101
Get/Set
Keypad Disable
BOOL
0=Not Disabled; 1=Disabled
115
Get
Warning Status
WORD
Bits 0-4 = reserved
Bit 5 = CP Warning
Bit 6 = IO Warning
Bit 7 = reserved
Bit 8 = reserved
Bit 9 = DN Warning
Bits 10-12 = reserved
Bit 13 = HW Warning
Bits 14-15 = reserved
124
Get/Set
Trip Enable
WORD
Bit enumerated trip enable word
130
Get/Set
Trip Reset Mode
BOOL
0=manual; 1=auto
131
Get/Set
Trip Reset Level
USINT
0 – 100%; default = 75
151
Get
Base Enclosure
WORD
Bit 0 = IP67
Bits 1-15 reserved
152
Get
Base Options
WORD
Bit 0 = reserved
Bit 1 = reserved
Bit 2 = CP Fuse Detect
Bits 3-7 = reserved
Bit 8 = 10A Base
Bit 9 = 25A Base
Bit 10-15 = reserved
153
Get
Wiring Options
WORD
Bit 0 = reserved
Bit 1 = reserved
Bit 2= 28xG Gland
Bits 3-15 = reserved
154
Get
Starter Enclosure
WORD
Bit 0 = IP67
Bits 1-15 reserved
155
Get
Starter Options
WORD
Bit 0 = Full Keypad
Bit 1 = Safety Monitor
Bits 2-15 reserved
156
Get
Last Pr Trip
UINT
See Parameter 61