beautypg.com

Frequency time – Rockwell Automation 284G ArmorStart - User Manual User Manual

Page 137

background image

Bulletin 284G Programmable Parameters for Sensorless Vector Controllers

4-57

A250 (Stp Logic Time 0)
A251 (Stp Logic Time 1)
A252 (Stp Logic Time 2)
A253 (Stp Logic Time 3)
A254 (Stp Logic Time 4)
A255 (Stp Logic Time 5)
A256 (Stp Logic Time 6)
A257 (Stp Logic Time 7)
Sets the time to remain in each step if the corresponding StpLogic command is set
to Step after Time.

Parameter Number

250…257

Related Parameters

138, 155, 158, 161,

171…177, 240…247

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.0 sec

Maximum Value

999.9 sec

Default Value

30.0 sec

EM Brk Off Delay
Sets the time the drive will remain at minimum frequency before ramping to the
commanded frequency and energizing the brake coil relay when Parameter 137 (Stop
Mode) is set to option 8 or 9.

Parameter Number

260

Related Parameters

137

Access Rule

GET/SET

Data Type

UNIT

Group

Advanced Setup

Units

0.01 sec

Minimum Value

0.01 sec

Maximum Value

10 sec

Default Value

0.0 sec

EM Brk On Delay
Sets the time the drive will remain at minimum frequency before stopping and de-
energizing the brake coil relay when Parameter 137 (Stop Mode) is set to option 8 or
9.

Parameter Number

261

Related Parameters

137

Access Rule

GET/SET

Data Type

UNIT

Group

Advanced Setup

Units

0.01 sec

Minimum Value

0.01 sec

Maximum Value

10.00 sec

Default Value

0.0 sec

Frequency

Time

Minimum Freq

260 [EM Brk Off Delay]

261 [EM Brk On Delay]

Stop

Commanded

Start

Commanded

EM Brk

De-Energized (On)

Drive Stops

EM Brk
Energized (Off)

Ramp Accel

Ramp Decel

This manual is related to the following products: