Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
4-57
A250 (Stp Logic Time 0)
A251 (Stp Logic Time 1)
A252 (Stp Logic Time 2)
A253 (Stp Logic Time 3)
A254 (Stp Logic Time 4)
A255 (Stp Logic Time 5)
A256 (Stp Logic Time 6)
A257 (Stp Logic Time 7)
Sets the time to remain in each step if the corresponding StpLogic command is set
to Step after Time.
Parameter Number
250…257
Related Parameters
138, 155, 158, 161,
171…177, 240…247
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.0 sec
Maximum Value
999.9 sec
Default Value
30.0 sec
EM Brk Off Delay
Sets the time the drive will remain at minimum frequency before ramping to the
commanded frequency and energizing the brake coil relay when Parameter 137 (Stop
Mode) is set to option 8 or 9.
Parameter Number
260
Related Parameters
137
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
0.01 sec
Minimum Value
0.01 sec
Maximum Value
10 sec
Default Value
0.0 sec
EM Brk On Delay
Sets the time the drive will remain at minimum frequency before stopping and de-
energizing the brake coil relay when Parameter 137 (Stop Mode) is set to option 8 or
9.
Parameter Number
261
Related Parameters
137
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
0.01 sec
Minimum Value
0.01 sec
Maximum Value
10.00 sec
Default Value
0.0 sec
Frequency
Time
Minimum Freq
260 [EM Brk Off Delay]
261 [EM Brk On Delay]
Stop
Commanded
Start
Commanded
EM Brk
De-Energized (On)
Drive Stops
EM Brk
Energized (Off)
Ramp Accel
Ramp Decel