3-22

Bulletin 280G/281G Programmable Parameters

Zone #4 Control

Zone 3 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages

Parameter Number

93

Access Rule

GET/SET

Data Type

BYTE

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

255

Default Value

3

Zone #1 Key

When the “Security Enable” bit
for zone 1 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 1.

Parameter Number

94

Access Rule

GET/SET

Data Type

UINT

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

65535

Default Value

0

Zone #2 Key

When the “Security Enable” bit
for zone 2 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 2.

Parameter Number

95

Access Rule

GET/SET

Data Type

UINT

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

65535

Default Value

0

Zone #3 Key

When the “Security Enable” bit
for zone 3 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 3.

Parameter Number

96

Access Rule

GET/SET

Data Type

UINT

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

65535

Default Value

0