Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
SW Current Trip
Enables/disables a software instantaneous (within 100 ms) current trip.
Parameter Number
198
Related Parameters
133
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 A
Minimum Value
0.0
Maximum Value
Drive rated amps x 2
Default Value
0.0 (Disabled)
Process Factor
Scales the output frequency value displayed by Parameter 110 (Process Display).
Output Freq x Process Factor = Process Display
Parameter Number
199
Related Parameters
110
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1
Minimum Value
0.1
Maximum Value
999.9
Default Value
30.0
Fault Clear
Resets a fault and clears the fault queue. Used primarily to clear a fault over
network communications.
0 = Ready/Idle (Default)
1 = Reset Fault
2 = Clear Buffer (Parameters 107…109 [Fault x Code])
Parameter Number
200
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
2
Default Value
0
Program Lock
Protects parameters against change by unauthorized personnel.
0 = Unlocked
1 = Locked
Parameter Number
201
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Testpoint Sel
Used by Rockwell Automation field service personnel.
Parameter Number
202
Related Parameters
119
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1 Hex
Minimum Value
0
Maximum Value
FFFF
Default Value
400
Stop drive before changing this parameter.