Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 113
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
4-33
Table 4.5
Analog Output Options
Note: Only options 5…14, 16, 17, 19, and 20 are not valid options.
Analog Out Sel
Sets the analog output signal (0…10V). The output is used to provide a signal that is
proportional to several drives
Parameter Number
165
Related Parameters
135, 166
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
See Table for details
Minimum Value
Maximum Value
Default Value
Options
Output Range
Minimum Output
Value
Maximum Output Value A066
(Analog Out High)
DIP Switch Position
Related
Parameter
0
OutFreq 0…10
0…10V
0V = 0 Hz
P035 (Maximum Freq)
0…10V
101
1
OutCurr 0…10
0…10V
0V = 0 Amps
200% Drive Rated Output Current
0…10V
103
2
OutVolt 0…10
0…10V
0V = 0 Volts
120% Drive Rated Output Volts
0…10V
104
3
OutPowr 0…10
0…10V
0V = 0 kW
200% Drive Rated Power
0…10V
122
4
TstData 0…10
0…10V
0V = 0000
65535 (Hex FFFF)
0…10V
119
5
OutFreq 0…20
0…20 mA
0 mA = 0 Hz
P035 (Maximum Freq)
0…20 mA
101
6
OutCurr 0…20
0…20 mA
0 mA = 0 Amps
200% Drive Rated Output Current
0…20 mA
103
7
OutVolt 0…20
0…20 mA
0 mA = 0 Volts
120% Drive Rated Output Volts
0…20 mA
104
8
OutPowr 0…20
0…20 mA
0 mA = 0 kW
200% Drive Rated Power
0…20 mA
122
9
TstData 0…20
0…20 mA
0 mA = 0000
65535 (Hex FFFF)
0…20 mA
119
10
OutFreq 4…20
4…20 mA
4 mA = 0 Hz
P035 (Maximum Freq)
0…20 mA
101
11
OutCurr 4…20
4…20 mA
4 mA = 0 Amps
200% Drive Rated Output Current
0…20 mA
103
12
OutVolt 4…20
4…20 mA
4 mA = 0 Volts
120% Drive Rated Output Volts
0…20 mA
104
13
OutPowr 4…20
4…20 mA
4 mA = 0 kW
200% Drive Rated Power
0…20 mA
122
14
TstData 4…20
4…20 mA
4 mA = 0000
65535 (Hex FFFF)
0…20 mA
119
15
OutTorq 0…10
0…10V
0V = 0 Amps
200% Drive Rated FLA
0…10V
129
16
OutTorq 0…20
0…20 mA
0 mA = 0 Amps
200% Drive Rated FLA
0…20 mA
129
17
OutTorq 4…20
4…20 mA
4 mA = 0 Amps
200% Drive Rated FLA
0…20 mA
129
18
Setpnt 0…10
0…10V
0V = 0%
100.0% Setpoint Setting
0…10V
209
19
Setpnt 0…20
0…20 mA
0 mA = 0%
100.0% Setpoint Setting
0…20 mA
209
20
Setpnt 4…20
4…20 mA
4 mA = 0%
100.0% Setpoint Setting
0…20 mA
209
Analog Out High
Scales the maximum output value for parameter 165 source setting
Parameter Number
166
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
%
Minimum Value
0%
Maximum Value
800%
Default Value
100%