Installation and Wiring

2-13

Wiring

Power, Control, and Ground Wiring

Table 2.1 provides the power, control, safety inputs, and ground wire
capacities, and the tightening torque requirements. The power,
control, ground, and safety monitor terminals will accept a maximum
of two wires per terminal.

Table 2.1

Power, Control, Safety Input, Ground Wire Size, and Torque

Specifications

Terminals

Wire Size

Torque

Wire Strip Length

Power

and

Ground

Primary/Secondary

Terminal:

1.5…4.0 mm

2

(#16 …#10 AWG)

Primary Terminal:

10.8 lb.-in.

(1.2 N•m)

Secondary Terminal:

4.5 lb.-in

(0.5 N•m)

0.35 in. (9 mm)

Control and Safety

Inputs

1.0 mm

2

…4.0 mm

2

(#18…#10 AWG)

6.2 lb.-in

(0.7 N•m)

0.35 in. (9 mm)