beautypg.com

Rockwell Automation 284G ArmorStart - User Manual User Manual

Page 254

background image

C-4

Bulletin 284G CIP Information

DeviceNet Object — CLASS CODE
0x0003

The following class attributes are supported for the DeviceNet Object:

Table C.7

DeviceNet Object Class Attributes

A single instance (Instance 1) of the DeviceNet Object will be
supported. The following instance attributes are supported:

Table C.8

DeviceNet Object Instance Attributes

See Table C.9

Table C.9

Allocation_byte

The following services are implemented for the DeviceNet Object:

Table C.10

DeviceNet Object Common Services

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

2

Attribute

ID

Access

Rule

Name

Data Type

Value

1

Get/Set

Node Address

USINT

0…63

2

Get/Set

Baud Rate

USINT

0 = 125K
1 = 250K
2 = 500K

5

Get

Allocation Info

• Allocation Choice
• Master Node Addr

Structure of:

• BYTE
• USINT

Allocation_byte ➊
0…63 = address
255 = unallocated

8

Get

MAC ID Switch Value

BOOL

0…63

Bit 0

Explicit messaging

Bit 1

Polled I/O

Bit 4

COS I/O

Bit 5

Cyclic I/O

Bit 6

Acknowledge Suppression

Service

Code

Implemented for

Service

Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x4B

No

Yes

Allocate_Master/Slave _Connection_Set

0x4C

No

Yes

Release_Master/Slave _Connection_Set