Bulletin 284G Programmable Parameters for Sensorless Vector Controllers

4-41

Figure 4.4 Overload Trip Curves

Figure 4.5

Motor OL Select
Drive provides Class 10 motor overload protection. Setting 0…2 select the derating

factor for I

2

t overload function.

0 = No Derate
1 = Min. Derate
2 = Max. Derate

Parameter Number

190

Related Parameters

132, 133

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1

Minimum Value

0

Maximum Value

2

Default Value

0

% of P132 (Motor NP Hertz)

% of P132 (Motor NP Hertz)

% of P132 (Motor NP Hertz)

% of P133 (Motor OL Current)

% of P133 (Motor OL Current)

% of P133 (Motor OL Current)

PWM Frequency
Sets the carrier frequency the PWM output waveform. The Figure 4.5 provides
derating guidelines based on the PWM frequency setting.

Parameter Number

191

Related Parameters

224

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.l Hz

Minimum Value

2.0 Hz

Maximum Value

16.0 Hz

Default Value

4.0 Hz