Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 174

8-2
ArmorStart® ZIP Configuration
Param #
Parameter Name
Parameter Description
67
AutoRun ZIP
Enables ZIP data production on power up
0=Disable; 1=Enable
68
Zone ProducedEPR
The Expected Packet Rate in msec. Defines the rate of at which ZIP data is produced. Defaults to 75 msec.
69
Zone ProducedPIT
The Production Inhibit Time in msec. Defines the minimum time between Change of State data production
70
Zone #1 MacId
The node address of the device whose data is to be consumed for zone 1
71
Zone #2 MacId
The node address of the device whose data is to be consumed for zone 2
72
Zone #3 MacId
The node address of the device whose data is to be consumed for zone 3
73
Zone #4 MacId
The node address of the device whose data is to be consumed for zone 4
74
Zone #1 Health
Read Only consumed connection status for zone 1
0=Healthy; 1=Not Healthy
75
Zone #2 Health
Read Only consumed connection status for zone 2
0=Healthy; 1=Not Healthy
76
Zone #3 Health
Read Only consumed connection status for zone 3
0=Healthy; 1=Not Healthy
77
Zone #4 Health
Read Only consumed connection status for zone 4
0=Healthy; 1=Not Healthy
78
Zone #1 Mask
Bit enumerated consumed data mask for zone 1. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit
is set, the corresponding consumed data byte is placed in the DeviceLogix data table
79
Zone #2 Mask
Bit enumerated consumed data mask for zone 2. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit
is set, the corresponding consumed data byte is placed in the DeviceLogix data table
80
Zone #3 Mask
Bit enumerated consumed data mask for zone 3. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit
is set, the corresponding consumed data byte is placed in the DeviceLogix data table
81
Zone #4 Mask
Bit enumerated consumed data mask for zone 4. Each bit represents a byte in consumed data up to 8 bytes in length. If a mask bit
is set, the corresponding consumed data byte is placed in the DeviceLogix data table
82
Zone #1 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 1.
83
Zone #2 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 2.
84
Zone #3 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 3.
85
Zone #4 Offset
The byte offset into the ZIP data portion of the DeviceLogix data table to place the chosen consumed data bytes for zone 4.
86
Zone #1 EPR
The Expected Packet Rate in msec. for the zone 1 consuming connection. If consumed data is not received in 4 times this value, the
zone connection will time out and “Zone #1 Health” will report 1 = Not Healthy.
87
Zone #2 EPR
The Expected Packet Rate in msec. for the zone 2 consuming connection. If consumed data is not received in 4 times this value, the
zone connection will time out and “Zone #2 Health” will report 1 = Not Healthy
88
Zone #3 EPR
The Expected Packet Rate in msec. for the zone 3 consuming connection. If consumed data is not received in 4 times this value, the
zone connection will time out and “Zone #3 Health” will report 1 = Not Healthy
89
Zone #4 EPR
The Expected Packet Rate in msec. for the zone 4 consuming connection. If consumed data is not received in 4 times this value, the
zone connection will time out and “Zone #4 Health” will report 1 = Not Healthy
90
Zone #1 Control
Zone 1 Control Word. Default Bit 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages.
91
Zone #2 Control
Zone 2 Control Word. Default Bit 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages.
92
Zone #3 Control
Zone 3 Control Word. Default Bit 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages.
93
Zone #4 Control
Zone 4 Control Word. Default Bit 1 set, all other bits clear.
Bit0=Security Enable 1=Enable data security
Bit1=COS Cnxn 1=Consume DNet Group 2 COS messages
Bit2=Poll Cnxn 1=Consume DNet Group 2 Poll Response msgs.
Bit3=Strobe Cnxn 1=Consume DNet Group 2 Strobe Response msgs.
Bit4=Multicast Poll 1=Consume Multicast Poll Response messages.
94
Zone #1 Key
When the “Security Enable” bit for zone 1 is enabled, this value must match the value of the Device Value Key parameter in the
device whose data is being consumed for zone 1.
95
Zone #2 Key
When the “Security Enable” bit for zone 1 is enabled, this value must match the value of the Device Value Key parameter in the
device whose data is being consumed for zone 2.
96
Zone #3 Key
When the “Security Enable” bit for zone 1 is enabled, this value must match the value of the Device Value Key parameter in the
device whose data is being consumed for zone 3.
97
Zone #4 Key
When the “Security Enable” bit for zone 1 is enabled, this value must match the value of the Device Value Key parameter in the
device whose data is being consumed for zone 4.
98
Device Value Key
This value is produced in the last 2 bytes of data when one of the ZIP assemblies is chosen for data production.
99
Zone Ctrl Enable
Global enable for ZIP peer-to-peer messaging. This parameter must be disabled before any changes to the ZIP configuration for the
device can be made. 0=Disable; 1=Enable