Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 176

8-4
ArmorStart® ZIP Configuration
The “Zone Mask” parameters (parameters 78-81) select individual
bytes within a consumed message for placement in the DeviceLogix
Data Table. Each single bit in the mask represents a corresponding
byte in the consumed message packet. For example, consider an
ArmorStart that has zone 1 configured to consume data from another
ArmorStart that is producing data of the following format:
The user can choose to place only bytes 1 and 2 of the above
consumed data in the DeviceLogix Data Table by selecting a Zone
Mask value of 00000011 binary as shown in the following
RSNetWorx for DeviceNet screen:
The “Zone Offset” parameters (parameters 82-85) determine where in
the DeviceLogix Data Table to place the consumed data bytes chosen
for mapping. The “Zone Offset” value corresponds to a byte in the
DeviceLogix Data Table where the data should be placed. Continuing
our example from above, a value of 2 in the “Zone #1 Offset”
parameter would result in the masked consumed data bytes being
placed starting at byte 2 in the data table. This would result in the
following ZIP bit assignments:
ZIP 16 = Zone 1: Tripped
ZIP 17 = Zone 1: Warning
Instance 163 Standard Produced Starter with Network Outputs and ZIP CCV
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
1
Ready
Running Rev Running Fwd Warning
Tripped
2
140M On
HOA
User In 4
User In 3
User In 2
User In 1
3
Net Out 8
Net Out 7
Net Out 6
Net Out 5
Net Out 4
Net Out 3
Net Out 2
Net Out 1
4
Net Out 15 Net Out 14 Net Out 13 Net Out 12 Net Out 11 Net Out 10
Net Out 9
5
Device Value Key (low)
6
Device Value Key (high)