Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 63

Bulletin 280G/281G Programmable Parameters
3-9
➊
Bulletin 280G products.
➋
Bulletin 281G products.
Produced I/O Size
This parameter reflects the
produced I/O data size in bytes.
Parameter Number
18
Access Rule
GET
Data Type
USINT
Group
DeviceNet
Units
—
Minimum Value
0
Maximum Value
8
Default Value
2
Starter COS Mask
This parameter allows the
installer to define the change-of-
state conditions that will result in
a change-of-state message
being produced
Parameter Number
19
Access Rule
GET/SET
Data Type
WORD
Group
DeviceNet
Units
—
Minimum Value
0
Maximum Value
16383
Default Value
16149
➊
16157
➋
Bit
Function
13
12
11
10
9
8
7
6
5
4
3
2
1
0
—
—
—
—
—
—
—
—
—
—
—
—
—
X
Tripped
—
—
—
—
—
—
—
—
—
—
—
—
X
—
Warning
—
—
—
—
—
—
—
—
—
—
X
—
—
Running Fwd
—
—
—
—
—
—
—
—
—
—
X
—
—
—
Running Rev
—
—
—
—
—
—
—
—
—
X
—
—
—
—
Ready
—
—
—
—
—
—
—
—
X
—
—
—
—
—
NET Ctl Status
—
—
—
—
—
—
—
X
—
—
—
—
—
—
140M On
—
—
—
—
—
—
X
—
—
—
—
—
—
—
Reserved
—
—
—
—
—
X
—
—
—
—
—
—
—
—
Input 0
—
—
—
—
X
—
—
—
—
—
—
—
—
—
Input 1
—
—
—
X
—
—
—
—
—
—
—
—
—
—
Input 2
—
—
X
—
—
—
—
—
—
—
—
—
—
—
Input 3
—
X
—
—
—
—
—
—
—
—
—
—
—
—
Input 4
X
—
—
—
—
—
—
—
—
—
—
—
—
—
Input 5