Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 128

4-48
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Figure 4.7
Current Limit 2
Maximum output current allowed before current limiting occurs. This parameter is
only active if Parameters 151, 152, 153, and 154 (Digital Inx Sel) is set to 25
Current Lmt2 and is active.
Parameter Number
218
Related Parameters
133, 151, 152, 153, 154, 189
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 A
Minimum Value
0.1 A
Maximum Value
Drive rated amps x 1.8
Default Value
Drive rated amps x 1.5
Skip Frequency
Sets the frequency at which the drive will not operate.
Parameter Number
219
Related Parameters
220
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 hz
Minimum Value
0.0
Maximum Value
400.0 Hz
Default Value
0.0 Hz
Skip Frq Band
Determines the brand width around Parameter 219 (Skip Frequency). Parameter
220 (Skip Frquency) is split applying 1/2 above and 1/2 below the actual skip
frequency. A setting of 0.0 disables this parameter.
Parameter Number
220
Related Parameters
219
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 Hz
Minimum Value
0.0 Hz
Maximum Value
30.0 Hz
Default Value
0.0 Hz