beautypg.com

Custom parameter based word- wise i/o assembly, Word-wise bit-packed assemblies – Rockwell Automation 284G ArmorStart - User Manual User Manual

Page 256

background image

C-6

Bulletin 284G CIP Information

Custom Parameter Based Word-
Wise I/O Assembly

Table C.13 CustomParameter Based Word Wise (Produced) Assembly

Instance

Word-Wise Bit-Packed Assemblies

Assemblies whose instance numbers are 180...189 are all one word
(16 bits) long. They can be used stand-alone, but their main use is to
assemble information for EDS file parameters. These Word-Wise
assemblies become the building blocks for the Custom Parameter
Based Word-Wise assembly described in Table C.13.

Table C.14

Instance 181 — Hardware Inputs 1…16

Table C.15

Instance 182 — Consumed Network Inputs 1…16

Table C.16 Instance 183 — Produced Network Outputs 1…15

Instance 120

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

0

Value of the parameter pointed to by Produced Word 0 Param (low byte)

1

Value of the parameter pointed to by Produced Word 0 Param (high byte)

1

2

Value of the parameter pointed to by Produced Word 1 Param (low byte)

3

Value of the parameter pointed to by Produced Word 1 Param (high byte)

2

4

Value of the parameter pointed to by Produced Word 2 Param (low byte)

5

Value of the parameter pointed to by Produced Word 2 Param (high byte)

3

6

Value of the parameter pointed to by Produced Word 3 Param (low byte)

7

Value of the parameter pointed to by Produced Word 3 Param (high byte)

Instance 181 — This is a Read Only Status Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Input 5

Input 4

Input 3

Input 2

Input 1

Input 0

1

Instance 182 — This is a Read/Write Control Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Net Input

8

Net Input

7

Net Input

6

Net Input

5

Net Input

4

Net Input

3

Net Input

2

Net Input

1

1

Net Input

16

Net Input

15

Net Input

14

Net Input

13

Net Input

12

Net Input

11

Net Input

10

Net Input

9

Instance 183 — This is a Read Only Status Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Net Out 8

Net Out

7

Net Out

6

Net Out

5

Net Out

4

Net Out

3

Net Out

8

Net Out

1

1

Reserved

Net Out

15

Net Out

14

Net Out

13

Net Out

12

Net Out

11

Net Out

10

Net Out

9