beautypg.com

Programming the 1756-controllogix, I/o mapping – Rockwell Automation 284G ArmorStart - User Manual User Manual

Page 158

background image

6-8

Explicit Messaging on DeviceNet™

Programming the
1756-ControlLogix

I/O Mapping

The following example will use the standard distributed motor
controller and the factory default input and output assembly of 160
and 161. Refer to Appendix B for additional assembly formats. The
default input and output assembly will again be used in the following
example.

Note: The addressing is different between the SLC 1747 and

ControlLogix 1756 program. It is important that the user
understand how to create and use “tags” in order to properly
follow the example. Please see the RSLogix™ 5000
programming manual for additional help with defining tags.

The tables below list the data configuration for the ControlLogix
platform and include the tag name as used in the example program.

Table 6.9

Example ControlLogix Input Addressing (Produced Assembly)

)

Table 6.10 Example ControlLogix Output Address (Consumed Assembly)

)

Instance 161 Default Produced Standard Distributed Motor Controller

Byte 0

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Address

Local:1:I.

Data[1].7

Local:1:I.

Data[1].6

Local:1:I.

Data[1].5

Local:1:I.

Data[1].4

Local:1:I.

Data[1].3

Local:1:I.

Data[1].2

Local:1:I.

Data[1].1

Local:1:I.

Data[1].0

Tag Name

Status_

warning

Status_

tripped

Data

reserved

reserved

reserved

Ready

Running Rev

Running Fwd

Warning

Tripped

Byte 1

Bit 15

Bit 14

Bit 13

Bit 12

Bit 11

Bit 10

Bit 9

Bit 8

Address

Local:1:I.

Data[1].15

Local:1:I.

Data[1].14

Local:1:I.

Data[1].13

Local:1:I.

Data[1].12

Local:1:I.

Data[1].11

Local:1:I.

Data[1].10

Local:1:I.

Data[1].9

Local:1:I.

Data[1].8

Tag Name

140M On

Data

reserved

reserved

User In 5

User In 4

User In 3

User In 2

User In 1

User In 0

Instance 160 Default Consumed Standard Distributed Motor Controller

Byte 0

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Address

Local:1:O.

Data[1].7

Local:1:O.

Data[1].6

Local:1:O.

Data[1].5

Local:1:O.

Data[1].4

Local:1:O.

Data[1].3

Local:1:O.

Data[1].2

Local:1:O.

Data[1].1

Local:1:O.

Data[1].0

Tag Name

Control_fault

Reset

Data

reserved

reserved

reserved

reserved

reserved

Fault Reset

Run Rev

Run Fwd

This manual is related to the following products: