Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
4-47
Slip Hertz @ FLA
Compensates for the inherent slip in an induction motor. This frequency is added to
the commanded output frequency based on motor current.
Parameter Number
214
Related Parameter
133
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 Hz
Minimum Value
0.0 Hz
Maximum Value
10.0 Hz
Default Value
2.0 Hz
Process Time Lo
Scales the time value when the drive is running at Parameter 134 (Minimum Freq).
When set to a value other than zero, Parameter 110 (Process Display) indicates the
duration of the process.
Parameter Number
215
Related Parameters
110, 134
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
Hz
Minimum Value
0.00
Maximum Value
99.99
Default Value
0.00
Process Time Hi
Scales the time value when the drive is running at Parameter 135 (Maximum Freq).
When set to a value other than zero, Parameter 110 (Process Display) indicates the
duration of the process.
Parameter Number
216
Related Parameters
110, 135
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
Hz
Minimum Value
0.00
Maximum Value
99.99
Default Value
0.00
Bus Reg Mode
Enables the bus regulator.
0 = Disable
1 = Enabled
Parameter Number
217
Related Parameters
Access Rule
GET/SET
Data Type
UNIT
Group
Advanced Setup
Units
—
Minimum Value
0
Maximum Value
1
Default Value
1