Bulletin 280G/281G Programmable Parameters

Zone #1 EPR

The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #1 Health”
will report 1 = Not Healthy.

Parameter Number

86

Access Rule

GET/SET

Data Type

UINT

Group

ZIP Parameters

Units

msec

MinimumValue

0

Maximum Value

65535

Default Value

75

Zone #2 EPR

The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #2 Health”
will report 1 = Not Healthy.

Parameter Number

87

Access Rule

GET/SET

Data Type

UNIT

Group

ZIP Parameters

Units

msec

MinimumValue

0

Maximum Value

65535

Default Value

75

Zone #3 EPR

The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #3 Health”
will report 1 = Not Healthy.

Parameter Number

88

Access Rule

GET/SET

Data Type

UNIT

Group

ZIP Parameters

Units

msec

MinimumValue

0

Maximum Value

65535

Default Value

75

Zone #4 EPR

The Expected Packet Rate in
msec. for the zone 1 consuming
connection. If consumed data is
not received in 4 times this
value, the zone connection will
time out and “Zone #4 Health”
will report 1 = Not Healthy.

Parameter Number

89

Access Rule

GET/SET

Data Type

UNIT

Group

ZIP Parameters

Units

msec

MinimumValue

0

Maximum Value

65535

Default Value

75