Bulletin 280G/281G CIP Information
B-7
Table B.19 Instance 185 This is a “Read Only” Status Assembly
Table B.20 Instance 186 This is a “Read Only” Status Assembly
Table B.21 Instance 187 This is a “Read/Write” Assembly
Table B.22 Instance 189 This is a “Read-Only” Assembly
Standard Distributed Motor
Controller I/O Assemblies
Standard Distributed Motor Controller IO Assemblies are available
on all Starter Types.
Standard Distributed Motor Controller Output (Consumed)
Assemblies
Table B.23 Instance 3 is the required output (consumed) assembly defined in
the DeviceNet Motor Starter Profile
Instance 185 — Starter Status
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Ref
—
Net Ctl
Status
Ready
Running
Rev
Running
Fwd
Warning
Tripped
1
—
—
140M On
HOA
Stat.
Keypad
Hand
—
—
—
Instance 186 — DeviceNet Status
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
—
—
I/O Idle
I/O Flt
Exp Flt
I/O Cnxn Exp Cnxn
1
ZIP FLT
ZIP4 CNX ZIP3 FLT ZIP2 CNX ZIP2 FLT ZIP2 CNX ZIP1 FLT ZIP1 CNX
Instance 187 — Starter Control Bits
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
User Out
B
User Out
A
—
—
—
Fault
Reset
Run Rev Run Fwd
1
—
—
—
—
—
—
—
—
Instance 189 — Warning Status Bits
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
IO
Warning
Control
Power
Warning
—
—
PL
Warning
—
—
1
—
—
HW Warn
—
—
—
DN Warn PI Warn
Instance 3 — ODVA Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
—
—
—
—
—
—
Run Fwd