Bulletin 284G Programmable Parameters for Sensorless Vector Controllers

4-39

Figure 4.3

Start Boost
Sets the boost voltage (% of Parameter 131 [Motor NP Volts]) and redefines the Volts
per Hz curve when Parameter 184 (Boost Select) = 0 Custom V/Hz and Parameter
225 (Torque Perf Mode) = 0V/Hz.

Parameter Number

185

Related Parameters

131, 132, 134, 135, 184, 186,

187, 188, 225

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

1.1%

Minimum Value

0.0%

Maximum Value

25.0%

Default Value

2.5%

Parameter 131 (Motor NP Volts)

Parameter 188 (Maximum Voltage)

Parameter 134 (Minimum Freq)

Parameter 187 (Break Frequency)

Parameter 132 (Motor NP Hertz)

Parameter 135 (Maximum Freq)

Frequency

Voltage

Parameter 186 (Break V

oltage)

Parameter 186

(Start Boost)