beautypg.com

Rockwell Automation 284G ArmorStart - User Manual User Manual

Page 66

background image

3-12

Bulletin 280G/281G Programmable Parameters

StrtrDN FltState

This parameter in conjunction
with Parameter 27 defines how
the starter will respond when a
DeviceNet fault occurs. When set
to “1”, hold to last state occurs.
When set to “0”, will go to DnFlt
Value on DN faults as determined
by Parameter 27.

Parameter Number

26

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN FltValue

This parameter determines how
the starter will be commanded in
the event of a Device Net fault.
0 = OFF
1 = ON

Parameter Number

27

Access Rule

GET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN IdlState

This parameter in conjunction
with Parameter 29 defines how
the starter will respond when a
DeviceNet network is idle. When
set to “1”, hold to last state
occurs. When set to “0”, will go
to DnIdl Value on DN Idle as
determined by Parameter 29.

Parameter Number

28

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

StrtrDN IdlValue

This parameter determines the
state that starter assumes when
the network is idle and
Parameter 28 is set to “0”
0 = OFF
1 = ON

Parameter Number

29

Access Rule

GET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

This manual is related to the following products: