Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
4-31
Table 4.4
Parameter 158 and 161 Options
Relay Out Level
Sets the trip point for the digital output relay if the value of Parameter 155 (Relay
Out Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.
Parameter Number
156
Related Parameters
155, 158, 161
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1
Minimum Value
0.0
Maximum Value
9999
Default Value
0.0
Parameters 155 Setting
Parameter 156 Min./Max.
6
0/400 Hz
7
0/180%
8
0/815V
10
0/100%
16
0.1/9999 sec
17
1/9999 counts
18
1/180
°
20
0/1
158 (Opto Out1 Sel)
161 (Opto Out2 Sel)
Determines the operation of the programmable opto outputs.
Parameter Number
158, 161
Related Parameters
133, 156, 192, 240…247,
250…257
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
See Table 4.4 for details
Minimum Value
Maximum Value
Default Value
Options
Description
0
Ready/Fault
(Default)
Opto outputs are active when power is applied. This indicates the drive is ready for operation. Opto outputs are
inactive when power is removed or a fault occurs.
1
At Frequency
(Parameter 161
Default)
Drive reached commanded frequency.
2
MotorRunning
(Parameter
158Default)
Motor is receiving power from drive.
3
Reverse
Drive is commanded to run in reverse direction.
4
Motor Overld
Motor overload condition exists.
5
Ramp Reg
Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from
occurring.
6
Above Freq
Drive exceeds the frequency (Hz) value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2
Level) Use Parameter 159 or 162 to set threshold.
7
Above Cur
Drive exceeds the current (% Amps) value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output
2 Level). Use Parameter 159 or 162 to set threshold. Important: Value for Parameter 159 or 162 must entered in
percent of the drive rated output current.
8
Above DCVolt
Drive exceeds the DC bus voltage value set in Parameter 159 (Opto Out 1 Level). Use Parameter 159 or 162 to set
threshold.
9
Retries Exst
Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
10
Above Anlg V
Option not valid for Bulletin 284G ArmorStart.
11
Logic In 1
An input is programmed as Logic In 1 and is active.
12
Logic In 2
An input is programmed as Logic In 2 and is active.
13
Logic In 1 & 2
Both Logic inputs are programmed and active.
14
Logic In 1 or 2
One or both Logic inputs are programmed and one or both is active.