beautypg.com

Rockwell Automation 284G ArmorStart - User Manual User Manual

Page 111

background image

Bulletin 284G Programmable Parameters for Sensorless Vector Controllers

4-31

Table 4.4

Parameter 158 and 161 Options

Relay Out Level
Sets the trip point for the digital output relay if the value of Parameter 155 (Relay
Out Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.

Parameter Number

156

Related Parameters

155, 158, 161

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1

Minimum Value

0.0

Maximum Value

9999

Default Value

0.0

Parameters 155 Setting

Parameter 156 Min./Max.

6

0/400 Hz

7

0/180%

8

0/815V

10

0/100%

16

0.1/9999 sec

17

1/9999 counts

18

1/180

°

20

0/1

158 (Opto Out1 Sel)
161 (Opto Out2 Sel)
Determines the operation of the programmable opto outputs.

Parameter Number

158, 161

Related Parameters

133, 156, 192, 240…247,

250…257

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

See Table 4.4 for details

Minimum Value

Maximum Value

Default Value

Options

Description

0

Ready/Fault

(Default)

Opto outputs are active when power is applied. This indicates the drive is ready for operation. Opto outputs are
inactive when power is removed or a fault occurs.

1

At Frequency

(Parameter 161

Default)

Drive reached commanded frequency.

2

MotorRunning

(Parameter

158Default)

Motor is receiving power from drive.

3

Reverse

Drive is commanded to run in reverse direction.

4

Motor Overld

Motor overload condition exists.

5

Ramp Reg

Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from
occurring.

6

Above Freq

Drive exceeds the frequency (Hz) value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2
Level) Use Parameter 159 or 162 to set threshold.

7

Above Cur

Drive exceeds the current (% Amps) value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output
2 Level). Use Parameter 159 or 162 to set threshold. Important: Value for Parameter 159 or 162 must entered in
percent of the drive rated output current.

8

Above DCVolt

Drive exceeds the DC bus voltage value set in Parameter 159 (Opto Out 1 Level). Use Parameter 159 or 162 to set
threshold.

9

Retries Exst

Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.

10

Above Anlg V

Option not valid for Bulletin 284G ArmorStart.

11

Logic In 1

An input is programmed as Logic In 1 and is active.

12

Logic In 2

An input is programmed as Logic In 2 and is active.

13

Logic In 1 & 2

Both Logic inputs are programmed and active.

14

Logic In 1 or 2

One or both Logic inputs are programmed and one or both is active.

This manual is related to the following products: