Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17

84

12

Error messages

12.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

EtherNet/IP: Internal error [0x00c86100]

EtherNet/IP: Internal error [0x00c86101]

EtherNet/IP: Invalid parameter set [0x00c8641f]

EtherNet/IP: Lenze setting loaded [0x00c86420]

EtherNet/IP: Internal mapping error [0x00c86430]

EtherNet/IP: Invalid IP parameters [0x00c86533]

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication module is defective.

Send communication module with error description to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication module is defective.

Send communication module with error description to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

No active parameter set could be loaded.

• Download application again (including module).

• Send communication module together with a

description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Access to parameter set in memory module via standard

device was not successful.

• Download application again (including module).

• Send communication module together with a

description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The entered I/O data mapping is invalid.

• An object not supporting the required properties has

been specified.

• More than 64 bytes of data have been mapped.

Repeat

I/O configuration in the »Engineer« ( 55)

.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

One or more IP parameters are faulty.

Check and correct IP configuration.

Setting the IP configuration of the Servo Drive 9400

( 37)