C13881 | overall ethernet timeout time, C13885 | clear i/o data, C13899 | hostname – Lenze E94AYCEO User Manual
Page 102: C13900 | firmware product type, C13901 | firmware compilation date, C13902 | firmware version, C13885, C13881, 13 parameter reference

Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
102
13
Parameter reference
13.2
Parameters of the communication module for slot MXI1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13881
C13885
C13899
C13900
C13901
C13902
Parameter | Name:
C13881 | Overall Ethernet Timeout Time
Data type: UNSIGNED_16
Index: 10694 = 0x29C6
Setting of the overall monitoring time (see
Fault with regard to EtherNet/IP communication ( 74)
)
A change in the monitoring response becomes immediately effective.
Setting range
(min. value | unit | max. value)
Lenze setting
500
ms
65535 10000 ms
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear I/O Data
Data type: UNSIGNED_8
Index: 10690 = 0x29C2
Setting which I/O data are to be processed by the adapter to maintain internal communication if ...
• the network status of the controlling I/O connection is "Not connected" (see
• an idle event has occurred.
Changes in the setting becomes effective immediately.
Fault with regard to EtherNet/IP communication ( 74)
Selection list
(Lenze setting printed in bold)
0 Use of last Scanner Output Data
1 Clear Scanner Output Data
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Hostname
Data type: VISIBLE_STRING
Index: 10676 = 0x29B4
Each subcode contains a string with a length of 64 bytes indicating the designation of the EtherNet/IP node.
(Instance attribute 6 (Host Name) in the
TCP/IP Interface Object (245 / 0xF5) ( 132)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13900 | Firmware Product Type
Data type: VISIBLE_STRING
Index: 10675 = 0x29B3
The code contains a string with a length of 8 bytes. The identification code "E84DGFCG" is displayed.
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13901 | Firmware Compilation Date
Data type: VISIBLE_STRING
Index: 10674 = 0x29B2
The code contains a string with a length of 20 bytes. The software creation date ("MMM DD YYYY") and time
("hh:mm:ss") are displayed (e.g. "Mar 21 2005 12:31:21").
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13902 | Firmware Version
Data type: VISIBLE_STRING
Index: 10673 = 0x29B1
The code contains a string with a length of 11 bytes. The firmware version is displayed (e.g. "00.01.00.00").
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT