C14858 | ethernet port statistics, C14861 | cip module status, C14862 | cip network status – Lenze E94AYCEO User Manual
Page 111: C14861, C14862, 13 parameter reference
13
Parameter reference
13.3
Parameters of the communication module for slot MXI2
111
Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14858
C14861
C14862
Parameter | Name:
C14858 | Ethernet Port Statistics
Data type: UNSIGNED_32
Index: 9717 = 0x25F5
Display of statistical values for the data transfer via the Ethernet connections
Subcodes
Info
C14858/1
Ethernet port X233: RX
C14858/2
Ethernet port X233: RX CRC error
C14858/3
Ethernet port X233: RX rejected
C14858/4
Ethernet port X233: TX
C14858/5
Ethernet port X233: TX rejected
C14858/6
Ethernet port X234: RX
C14858/7
Ethernet port X234: RX CRC error
C14858/8
Ethernet port X234: RX rejected
C14858/9
Ethernet port X234: TX
C14858/10
Ethernet port X234: TX rejected
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14861 | CIP Module Status
Data type: UNSIGNED_16
Index: 9714 = 0x25F2
Display of the current CIP module status
(Instance attribute 8 (State) in the
Identity Object (1 / 0x01) ( 121)
• The status is also indicated via the MS LED.
Selection list
(read only)
0 Nonexistent
1 Device Self Testing
2 Standby
3 Operational
4 Major Recoverable Fault
5 Major Unrecoverable Fault
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14862 | CIP Network Status
Data type: UNSIGNED_16
Index: 9713 = 0x25F1
Display of the current CIP network status
• The status is also indicated via the NS LED.
Selection list
(read only)
0 No IP Address
1 Nonexistent
2 Established
3 Timed Out
4 Duplicate IP
5 Self-Test
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT