beautypg.com

C14881 | overall ethernet timeout time, C14885 | clear i/o data, C14899 | hostname – Lenze E94AYCEO User Manual

Page 115: C14900 | firmware product type, C14901 | firmware compilation date, C14902 | firmware version, C14885, C14881, Is set, 13 parameter reference

background image

13

Parameter reference

13.3

Parameters of the communication module for slot MXI2

115

Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14881

C14885

C14899

C14900

C14901

C14902

Parameter | Name:

C14881 | Overall Ethernet Timeout Time

Data type: UNSIGNED_16

Index: 9694 = 0x25DE

Setting of the overall monitoring time (see

Fault with regard to EtherNet/IP communication ( 74)

)

A change in the monitoring response becomes immediately effective.
Setting range

(min. value | unit | max. value)

Lenze setting

500

ms

65535 10000 ms

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14885 | Clear I/O Data

Data type: UNSIGNED_8

Index: 9690 = 0x25DA

Setting which I/O data are to be processed by the adapter to maintain internal communication if ...

• the network status of the controlling I/O connection is "Not connected" (see

C14862

) or

• an idle event has occurred.

Changes in the setting becomes effective immediately.

(See

Fault with regard to EtherNet/IP communication ( 74)

.)

Selection list

(Lenze setting printed in bold)

0 Use of last Scanner Output Data
1 Clear Scanner Output Data

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14899 | Hostname

Data type: VISIBLE_STRING

Index: 9676 = 0x25CC

Each subcode contains a string with a length of 64 bytes indicating the designation of the EtherNet/IP node.

(Instance attribute 6 (Host Name) in the

TCP/IP Interface Object (245 / 0xF5) ( 132)

)

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14900 | Firmware product type

Data type: VISIBLE_STRING

Index: 9675 = 0x25CB

The code contains a string with a length of 8 bytes. The identification code "E94AYCEO" is output.

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14901 | Firmware compilation date

Data type: VISIBLE_STRING

Index: 9674 = 0x25CA

The code contains a string with a length of 20 bytes. The software creation date ("MMM DD YYYY") and time

("hh:mm:ss") are displayed (e.g. "Mar 21 2005 12:31:21").

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14902 | Firmware version

Data type: VISIBLE_STRING

Index: 9673 = 0x25C9

The code contains a string with a length of 11 bytes. The firmware version is displayed (e.g. "00.01.00.00").

Read access  Write access  CINH  PLC STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT