C14881 | overall ethernet timeout time, C14885 | clear i/o data, C14899 | hostname – Lenze E94AYCEO User Manual
Page 115: C14900 | firmware product type, C14901 | firmware compilation date, C14902 | firmware version, C14885, C14881, Is set, 13 parameter reference
13
Parameter reference
13.3
Parameters of the communication module for slot MXI2
115
Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14881
C14885
C14899
C14900
C14901
C14902
Parameter | Name:
C14881 | Overall Ethernet Timeout Time
Data type: UNSIGNED_16
Index: 9694 = 0x25DE
Setting of the overall monitoring time (see
Fault with regard to EtherNet/IP communication ( 74)
)
A change in the monitoring response becomes immediately effective.
Setting range
(min. value | unit | max. value)
Lenze setting
500
ms
65535 10000 ms
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14885 | Clear I/O Data
Data type: UNSIGNED_8
Index: 9690 = 0x25DA
Setting which I/O data are to be processed by the adapter to maintain internal communication if ...
• the network status of the controlling I/O connection is "Not connected" (see
• an idle event has occurred.
Changes in the setting becomes effective immediately.
Fault with regard to EtherNet/IP communication ( 74)
Selection list
(Lenze setting printed in bold)
0 Use of last Scanner Output Data
1 Clear Scanner Output Data
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14899 | Hostname
Data type: VISIBLE_STRING
Index: 9676 = 0x25CC
Each subcode contains a string with a length of 64 bytes indicating the designation of the EtherNet/IP node.
(Instance attribute 6 (Host Name) in the
TCP/IP Interface Object (245 / 0xF5) ( 132)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14900 | Firmware product type
Data type: VISIBLE_STRING
Index: 9675 = 0x25CB
The code contains a string with a length of 8 bytes. The identification code "E94AYCEO" is output.
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14901 | Firmware compilation date
Data type: VISIBLE_STRING
Index: 9674 = 0x25CA
The code contains a string with a length of 20 bytes. The software creation date ("MMM DD YYYY") and time
("hh:mm:ss") are displayed (e.g. "Mar 21 2005 12:31:21").
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14902 | Firmware version
Data type: VISIBLE_STRING
Index: 9673 = 0x25C9
The code contains a string with a length of 11 bytes. The firmware version is displayed (e.g. "00.01.00.00").
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT