beautypg.com

5 protective insulation, Protective insulation, 4technical data – Lenze E94AYCEO User Manual

Page 19

background image

4

Technical data

4.5

Protective insulation

19

Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.5

Protective insulation

Danger!

Dangerous voltage
If the Servo Drives 9400 are operated on a phase earthed mains with a rated mains

voltage  400 V, external measures need to be implemented in order to ensure

protection against accidental contact.
Possible consequences:
Death or severe injuries
Protective measures:
If protection against accidental contact is required for the control terminals of the

inverter and the connections of the plugged device modules, ...

• a double isolating distance must exist.
• the components to be connected must be provided with the second isolating

distance.

Note!

The protective insulation provided in Servo Drives 9400 is implemented in accordance

with EN 61800-5-1.