ETC Echo Architectural Control Processor (ACP) v1.0.0 User Manual
Page 74
69
Echo ACP Configuration Manual
2 and 3 Wire Fluorescent Mode
Property
Units
Default 120V
Default 230V
Default 277V
Curve
not applicable Linear
Linear
Linear
Voltage Regulation
On / Off
On
On
On
Dynamic Preheat
Seconds / Off
Off
Off
Off
Min Scale
Volts
56V
108V
130V
Max Scale
Volts
120V
230V
277V
Transformer Mode
On / Off
On
On
On
Threshold
Control
1% (>0%)
1% (>0%)
1% (>0%)
4 Wire Fluorescent Mode
Property
Units
Default 120V
Default 230V
Default 277V
Curve
not applicable Linear
Linear
Linear
Voltage Regulation
On / Off
Off
Off
Off
Dynamic Preheat
Seconds / Off
Off
Off
Off
Min Scale
Volts
120 =Max
230 =Max
277 =Max
Max Scale
Volts
120
230
277
Transformer Mode
On / Off
On
On
On
Threshold
Control
1% (>0%)
1% (>0%)
1% (>0%)
Always On Mode
Property
Units
Default 120V
Default 230V
Default 277V
Curve
not applicable Linear
Linear
Linear
Voltage Regulation
On / Off
Off
Off
Off
Dynamic Preheat
Seconds / Off
Off
Off
Off
Min Scale
Volts
0
0
0
Max Scale
Volts
120
230
277
Transformer Mode
On / Off
Off
Off
Off
Threshold
Control
0
0
0
DALI Mode
Property
Units
Default 120V
Default 230V
Default 277V
Curve
not applicable Linear
Linear
Linear
Voltage Regulation
On / Off
Off
Off
Off
Dynamic Preheat
Seconds / Off
Off
Off
Off
Min Scale
Volts
0
0
0
Max Scale
Volts
120
230
277
Transformer Mode
On / Off
On
On
On
Threshold
Control
0
0
0