F.en.04 critical condition—transceiver removed, Voltage sensor and current sensor conditions – HP 3000 Enterprise Virtual Array User Manual
Page 149

0.F.en.02 CRITICAL Condition—Transceiver Data Signal Lost
This symptom can occur when a controller has been powered off or a cable has been removed from
the transceiver. The transceiver can no longer detect a data signal. This error prevents the controller
from transferring data on a loop and eliminates the enclosure dual-loop capability. This error remains
active until the problem is fixed.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service representative.
0.F.en.03 CRITICAL Condition—Transceiver FC-AL Bus Fault
The system has detected an FC-AL bus fault involving a transceiver. This error prevents the controller from
transferring data on a loop ad eliminates the enclosure dual-loop capability.
Complete the following procedure to correct this problem:
1.
Record all six characters of the condition report.
2.
Check all the transceivers and cables to ensure they are properly connected.
3.
Check all the transceivers on the loop to ensure they are compatible with the I/O module.
4.
If the problem persists, contact your HP authorized service representative.
0.F.en.04 CRITICAL Condition—Transceiver Removed
The EMU detects that a transceiver has been removed. This error remains active until the problem is fixed.
The error can be cleared by doing one of the following:
1.
Install a new transceiver,
or
Reconfigure the system by switching from a loop topology to one with Vixel switches, then the
transceiver is not necessary.
2.
Clear the error by resetting the EMU or by removing and then re-installing the I/O module.
0.F.en.05 CRITICAL Condition—Invalid Fibre Channel Character
This symptom can occur under the following conditions:
•
The incoming data stream is corrupted.
•
A cable is not completely connected.
•
The signal is degraded.
This error prevents the controller from transferring data on a loop and eliminates the enclosure dual-loop
capability. This error remains active until the problem is fixed.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service representative.
Voltage sensor and current sensor conditions
The format of these sensor condition reports is 1.2.en.ec for a voltage sensor, and 1.3.en.ec for a
current sensor, where:
•
1.2. is the voltage sensor element type
•
1.3. is the current sensor element type number
•
en. is the sensor element number
•
ec is the error code
lists the location of the power supply voltage and current sensors.
Enterprise Virtual Array 3000/5000 user guide (VCS 3.110)