Table 32 Environmental operating specifications
Ambient temperature
: +10 °C to +35 °C (+50 °F to +95 °F) with an
average rate of change of 1 °C/hour maximum and a step change of 3 °C
or less. Maintaining the optimum ambient temperature within the specified
range ensures that the internal operating temperatures support the drive
manufacturer’s MTBF specifications.
Relative humidity: 40% to 60% (noncondensing) with a step change of 10%
or less (noncondensing)
Air quality: Not to exceed a maximum of 500,000 particles, 0.5 micron or
larger, per cubic foot of air.
Heat dissipation: 1600 BTUs per hour
When shipping, or placing this product in short term storage, HP recommends maintaining the
environmental conditions listed in
Table 33 Environmental shipping or short-term storage specifications
Ambient temperature
: –40 °C to +66 °C (–40 °F to +151 °F)
Relative humidity: 10% to 80% noncondensing
Altitude: below 15,240 m (50,000 ft)
Power specifications
The input voltage to the drive enclosure power supplies is a function of the country-specific input voltage
to Enterprise storage system rack power distribution units (PDUs).
defines the AC input power
available to the drive enclosure power supplies.
CAUTION:
The AC power distribution within a rack ensures a balanced to each PDA and reduces the possibility of
an overload condition. Changing the cabling to or from a PDM could cause an overload condition.
Table 34 Enterprise storage system AC input line voltages
Specification
Minimal
Nominal
Maximum
60 Hz Service
AC Line Voltage
57 Hz
60 Hz
63 Hz
AC Line Voltage—Japan
180 VAC
202 VAC
220 VAC
AC Line Voltage–North America
180 VAC
208 VAC
220 VAC
AC Line Voltage–Europe
208 VAC
240 VAC
254 VAC
50 Hz Service
AC Line Frequency
47 Hz
50 Hz
53 Hz
AC Line Voltage–Japan
180 VAC
202 VAC
220 VAC
AC Line Voltage–North America
190 VAC
220 VAC
235 VAC
AC Line Voltage–North America
200 VAC
230 VAC
244 VAC
AC Line Voltage–Europe
208 VAC
240 VAC
254 VAC
defines the AC input current and wattage to the drive enclosure power supplies.