beautypg.com

Power specifications, Environmental operating specifications, Enterprise storage system ac input line voltages – HP 3000 Enterprise Virtual Array User Manual

Page 127

background image

Table 32 Environmental operating specifications

Ambient temperature

: +10 °C to +35 °C (+50 °F to +95 °F) with an

average rate of change of 1 °C/hour maximum and a step change of 3 °C

or less. Maintaining the optimum ambient temperature within the specified

range ensures that the internal operating temperatures support the drive

manufacturer’s MTBF specifications.
Relative humidity: 40% to 60% (noncondensing) with a step change of 10%

or less (noncondensing)
Air quality: Not to exceed a maximum of 500,000 particles, 0.5 micron or

larger, per cubic foot of air.
Heat dissipation: 1600 BTUs per hour

When shipping, or placing this product in short term storage, HP recommends maintaining the

environmental conditions listed in

Table 33

.

Table 33 Environmental shipping or short-term storage specifications

Ambient temperature

: –40 °C to +66 °C (–40 °F to +151 °F)

Relative humidity: 10% to 80% noncondensing
Altitude: below 15,240 m (50,000 ft)

Power specifications

The input voltage to the drive enclosure power supplies is a function of the country-specific input voltage

to Enterprise storage system rack power distribution units (PDUs).

Table 34

defines the AC input power

available to the drive enclosure power supplies.

CAUTION:

The AC power distribution within a rack ensures a balanced to each PDA and reduces the possibility of

an overload condition. Changing the cabling to or from a PDM could cause an overload condition.

Table 34 Enterprise storage system AC input line voltages

Specification

Minimal

Nominal

Maximum

60 Hz Service

AC Line Voltage

57 Hz

60 Hz

63 Hz

AC Line Voltage—Japan

180 VAC

202 VAC

220 VAC

AC Line Voltage–North America

180 VAC

208 VAC

220 VAC

AC Line Voltage–Europe

208 VAC

240 VAC

254 VAC

50 Hz Service

AC Line Frequency

47 Hz

50 Hz

53 Hz

AC Line Voltage–Japan

180 VAC

202 VAC

220 VAC

AC Line Voltage–North America

190 VAC

220 VAC

235 VAC

AC Line Voltage–North America

200 VAC

230 VAC

244 VAC

AC Line Voltage–Europe

208 VAC

240 VAC

254 VAC

Table 35

defines the AC input current and wattage to the drive enclosure power supplies.

Enterprise Virtual Array 3000/5000 user guide (VCS 3.110)

127