Power distribution

AC power is distributed to the rack through a dual Power Distribution Unit (PDU) assembly mounted at the

bottom rear of the rack. The characteristics of the fully-redundant rack power configuration are as follows:

Each PDU is connected to a separate circuit-breaker-protected, 30-A AC site power source

(220–240 VAC ±10%, 50 or 60 Hz, ±5%).

Figure 49

illustrates the compatible 60-Hz and

50-Hz wall receptacles.

CXO7549A

NEMA L6-30R receptacle, 3-wire, 30-A, 60-Hz

CXO5409B

IEC 309 receptacle, 3-wire, 30-A, 50-Hz

Figure 49 60-Hz and 50-Hz wall receptacles

The standard power configuration for any Enterprise Virtual Array rack is the fully redundant

configuration. Implementing this configuration requires:
• Two separate circuit-breaker-protected, 30-A site power sources with a compatible wall

receptacle (see

Figure 49

).

• One dual PDU assembly. Each PDU connects to a different wall receptacle.
• Eight Power Distribution Modules (PDM) per rack. Four PDMs mount vertically on each side of

the rack. Each set of four PDMs connects to a different PDU.

• The drive enclosure power supplies on the left (PS 1) connect to the PDMs on the left with a

gray, 66 cm (26 in) power cord.

• The drive enclosure power supplies on the right (PS 2) connect to the PDMs on the right with a

black, 66 cm (26 in) power cord.

• The upper controller connects to a PDM on the left with a gray, 152 cm (60 in) power cord.
• The lower controller connects to a PDM on the right with a black, 66 cm (26 in) power cord.

NOTE:

Drive enclosures, when purchased separately, include one 202 cm (80 in) black cable and one 202

cm (80 in) gray cable.

The configuration provides complete power redundancy and eliminates all single points of failure for

both the AC and DC power distribution.

PDUs

Each Enterprise Virtual Array rack has either a 50- or 60-Hz, dual PDU mounted at the bottom rear of the

rack. The 30–56205–03/30–56205–04 PDU placement is side-by-side. The 228481–002/228481–003

PDU placement is back-to-back, plugs facing out.

Enterprise Virtual Array 3000/5000 user guide (VCS 3.110)