En.03 noncritical condition—low temperature, En.04 critical condition—low temperature, En.05 unrecoverable condition—high temperature – HP 3000 Enterprise Virtual Array User Manual

Page 143

background image

4.

Ensure that both blowers are operating properly (the LEDs are on) and neither blower is operating

at high speed.

5.

Verify that the

ambient temperature

range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as

necessary.

6.

Observe the EMU to ensure the error is corrected.

7.

If unable to correct the problem, contact your authorized service representative.

0.4.en.03 NONCRITICAL condition—Low temperature

This condition report indicates that an element temperature is approaching, but has not reached, the low

temperature CRITICAL threshold. Continued operation under these conditions may result in a CRITICAL

condition. This condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem.

1.

Record all six characters of the condition report.

2.

Verify that the

ambient temperature

range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as

necessary.

3.

Observe the EMU to ensure the error is corrected.

4.

If the

ambient temperature

is correct and the problem persists, contact your Authorized Service

Representative.

0.4.en.04 CRITICAL condition—Low temperature

This condition report indicates that an element temperature has reached the low temperature CRITICAL

threshold. HP recommends correcting this error to prevent affecting other elements. This condition

report remains active until the problem is corrected.
Complete the following procedure to correct this problem:

1.

Record all six characters of the condition report.

2.

Verify that the

ambient temperature

range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as

necessary.

3.

Observe the EMU to ensure the error is corrected.

4.

If the

ambient temperature

is correct and the problem persists, contact your authorized service

representative.

0.4.en.05 UNRECOVERABLE condition—High temperature

This condition report indicates that the EMU has evaluated the temperature of the three temperature

groups (EMU, disk drives, and power supplies), and determined that the average temperature of two of

the three groups exceeds the critical level (use Command View EVA to view the temperature thresholds).

Under these conditions the EMU starts a timer that will automatically shut down the enclosure in seven

minutes unless you correct the problem. Enclosure shutdown is imminent!

CAUTION:

An automatic shutdown and possible data corruption may result if the procedure below is not performed

immediately.

Complete the following procedure to correct this problem:

1.

Ensure that all disk drives, I/O modules, and power supply elements are fully seated.

2.

Ensure that all blowers are operating properly.

3.

Verify that the

ambient temperature

range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as

necessary.

Enterprise Virtual Array 3000/5000 user guide (VCS 3.110)

143