Page 146

background image

0.7.01.11 NONCRITICAL condition—EMU NVRAM write failure

The EMU cannot write data to the NVRAM. This condition report remains active until the problem is

corrected.
Complete the following procedure to correct this problem:

1.

Record all six characters of the condition report.

2.

Reset the EMU.

3.

Observe the EMU to ensure the error is corrected.

4.

If resetting the enclosure did not correct the problem, contact your HP authorized service

representative.

0.7.01.12 NONCRITICAL condition—EMU cannot read NVRAM data

The EMU is unable to read data from the NVRAM. This condition report remains active until the problem

is corrected.
Complete the following procedure to correct this problem:

1.

Record all six characters of the condition report.

2.

Reset the EMU.

3.

Observe the EMU to ensure the error is corrected.

4.

If resetting the enclosure did not correct the problem, contact your HP authorized service

representative.

0.7.01.13 UNRECOVERABLE condition—EMU load failure

The EMU Field Programmable Gate Array (FPGA) that controls the ESI bus failed to load information

required for EMU operation. This condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem:

1.

Record all six characters of the condition report.

2.

Reset the EMU.

3.

Observe the EMU to ensure the error is corrected.

4.

If resetting the enclosure did not correct the problem, contact your HP authorized service

representative.

0.7.01.14 NONCRITICAL condition—EMU enclosure address

Either the enclosure address is incorrect or the enclosure has no address. Possible causes include a

defective enclosure address bus cable, an incorrectly connected cable, or a defective enclosure address

bus JB. This condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem:

1.

Record all six characters of the condition report.

2.

Remove and reconnect the cable between the address bus JB and the EMU.

NOTE:

The EMU display may not display a change in condition for up to 30 seconds.

3.

Observe the EMU to ensure the error is corrected.

4.

If the problem is not corrected, remove and reinstall the bottom and top terminators, and all the

JB-to-JB cables.

146