TECHNICAL DATA

152

IFC 300

www.krohne.com

08/2010 - 4000069803 - MA IFC 300 R04 en

Control input

Control input

Control input

Control input

Function

Hold value of the outputs (e.g. for cleaning work), set value of the outputs to "zero",

counter and error reset, range change.

Start of dosing when dosing function is activated.

Operating data

Basic I/Os

Basic I/Os

Basic I/Os

Basic I/Os

Modular I/Os

Modular I/Os

Modular I/Os

Modular I/Os

Ex i I/Os

Ex i I/Os

Ex i I/Os

Ex i I/Os

Active

-

U

int

= 24 VDC

Ext. contact open:

U

0, nom

= 22 V

Ext. contact closed:

I

nom

= 4 mA

Contact closed (on):

U

0

≥ 12 V

with I

nom

= 1.9 mA

Contact open (off):

U

0

≤ 10 V

with I

nom

= 1.9 mA

-

Passive

8 V ≤ U

ext

≤ 32 VDC

I

max

= 6.5 mA

at U

ext

≤ 24 VDC

I

max

= 8.2 mA

at U

ext

≤ 32 VDC

Contact closed (on):

U

0

≥ 8 V

with I

nom

= 2.8 mA

Contact open (off):

U

0

≤ 2.5 V

with I

nom

= 0.4 mA

3 V ≤ U

ext

≤ 32 VDC

I

max

= 9.5 mA

at U

ext

≤ 24 V

I

max

= 9.5 mA

at U

ext

≤ 32 V

Contact closed (on):

U

0

≥ 3 V

with I

nom

= 1.9 mA

Contact open (off):

U

0

≤ 2.5 V

with I

nom

= 1.9 mA

U

ext

≤ 32 VDC

I ≤ 6 mA at U

ext

= 24 V

I ≤ 6.6 mA at U

ext

= 32 V

On:

U

0

≥ 5.5 V or I ≥ 4 mA

Off:

U

0

≤ 3.5 V or I ≤ 0.5 mA

U

i

= 30 V

I

i

= 100 mA

P

i

= 1 W

C

i

= 10 nF

L

i

= 0 mH

NAMUR

-

Active to EN 60947-5-6

Terminals open:

U

0, nom

= 8.7 V

Contact closed (on):

U

0, nom

= 6.3 V

with I

nom

> 1.9 mA

Contact open (off):

U

0, nom

= 6.3 V

with I

nom

< 1.9 mA

Detection of cable break:

U

0

≥ 8.1 V with I ≤ 0.1 mA

Detection of cable short

circuit:

U

0

≤ 1.2 V with I ≥ 6.7 mA

-