Technical data – KROHNE IFC 300 Converter EN User Manual
Page 146

8
TECHNICAL DATA
146
IFC 300
www.krohne.com
08/2010 - 4000069803 - MA IFC 300 R04 en
Operating conditions
Temperature
Temperature
Temperature
Temperature
Process temperature
Refer to technical data for the measuring sensor.
Ambient temperature
Depending on the version and combination of outputs.
It is a good idea to protect the converter from external heat sources such as direct
sunlight as higher temperatures reduce the life cycle of all electronic components.
-40…+65°C / -40…+149°F
Ambient temperatures below -25°C / -13°F, may affect the readability of the display.
Storage temperature
-50…+70°C / -58…+158°F
Pressure
Pressure
Pressure
Pressure
Medium
Refer to technical data for the measuring sensor.
Ambient pressure
Atmosphere: Height up to 2000 m / 6561.7 ft
Chemical properties
Chemical properties
Chemical properties
Chemical properties
Electrical conductivity
Standard
Standard
Standard
Standard
All media except for water: ≥ 1 µS/cm
(also refer to the technical data for the measuring sensor)
Water: ≥ 20 µS/cm
TIDALFLUX 4000
TIDALFLUX 4000
TIDALFLUX 4000
TIDALFLUX 4000
All media: ≥ 50 µS/cm
(also refer to the technical data for the measuring sensor)
OPTIFLUX 7000
OPTIFLUX 7000
OPTIFLUX 7000
OPTIFLUX 7000
All media except for water: ≥ 0.05 µS/cm
(also refer to the technical data for the measuring sensor)
Water: ≥ 1 µS/cm
Physical condition
Conductive, liquid media
Solid content (volume)
Can be used up to ≤ 70% for OPTIFLUX and TIDALFLUX measuring sensors
The greater the solid content, the less accurate the measurements!
Gas content (volume)
Can be used up to ≤ 5% for OPTIFLUX and TIDALFLUX measuring sensors
The greater the gas content, the less accurate the measurements!
Flow
For detailed information, refer to chapter "Flow tables".
Other conditions
Other conditions
Other conditions
Other conditions
Protection category acc. to
IEC 529 / EN 60529
C (compact version) & F (field housing):
IP66/67 (acc. to NEMA 4/4X/6)
W (wall-mounted housing):
IP65/66 (acc. to NEMA 4/4X)
R (19" rack-mounted housing (28 TE) or (21 TE)):
IP20 (acc. to NEMA 1);
Use: Indoor only, level of pollution 2 and relative humidity < 75%
Installation conditions
Installation
For detailed information, refer to chapter "Installation conditions".
Inlet/outlet runs
Refer to technical data for the measuring sensor.
Dimensions and weights
For detailed information refer to chapter "Dimensions and weights".