beautypg.com

Operation – KROHNE IFC 300 Converter EN User Manual

Page 125

background image

OPERATION

6

125

IFC 300

www.krohne.com

08/2010 - 4000069803 - MA IFC 300 R04 en

C2.… status output X

C2.…

status output X

X (Y) stands for one of the connection terminals A, B, C or D

…

stands for Fct. no. C2.2 (A) / C2.3 (B) / C2.4 (C) / C2.5 (D)

C2.….1

mode

The output shows the following measuring conditions:

out of specification (output activated, signals application error or error in

device refer to

Status messages and diagnostic information

on page 135 /

application error (output activated, signals application error or error in

device refer to

Status messages and diagnostic information

on page 135 /

polarity flow (polarity of the current flow) /

over range flow (over range of the flow) /

counter 1 preset (activates when counter X preset value is reached) /

counter 2 preset (activates when counter X preset value is reached) /

counter 3 preset (activates when counter X preset value is reached) /

output A (activated by the status of output Y, additional output data see

below) /

output B (activated by the status of output Y, additional output data see

below) /

output C (activated by the status of output Y, additional output data see

below) /

output D (activated by the status of output Y, additional output data see

below) /

off (switched off) /

empty pipe (when pipe empty, output activated) (contains the low-level

detection for PF option (partly filled)) /

error in device (when error, output activated)

C2.….2

current out Y

Only appears if output A...C is set under "mode (see above)", and this output

is a "current output".

Select:

polarity (is signalled) /

over range (is signalled) /

automatic range signals lower range

C2.….2

frequency out Y and pulse

output Y

Only appears if output A, B or D is set under "mode (see above)", and this

output is a "frequency/pulse output".

Select:

polarity (is signalled) /

over range (is signalled)

C2.….2

status output Y

Only appears if output A...D is set under "mode (see above)", and this output

is a "status output".

Same signal (like other connected status output, signal can be inverted, see

below)

C2.….2

limit switch Y and control

input Y

Only appears if output A...D / input A or B is set under "mode (see above)",

and this output / input is a "limit switch / control input".

Status off (is always selected here if status output X is connected with a limit

switch / control input Y.

C2.….2

off

Only appears if output A...D is set under "mode (see above)" and this output

is switched off.

C2.….3

invert signal

Select:

off (activated output supplies a high current, switch closed) /

on (activated output supplies a low current, switch open)

C2.….4

information

Serial no. of the I/O board, software version no. and production date of the

circuit board

C2.….5

simulation

Sequence see B1.… status output X