Out of specification (NE 107 status signal)

ERR 102 Temperature Out of

Range

1

The ambient temperature is

outside the given range. This

can cause loss or corruption

of data.

Measure the ambient temperature. De-

energize the device until the ambient

temperature is back in the given range. If

the temperature does not stay in the

correct range, make sure that there is

insulation around the signal converter. If

this error occurs 2 times, replace the

device.

ERR 201 Overfill

2

The level is in the blocking

distance. There is a risk that

the product will overflow

and/or cover the device.

Remove some of the product until the level

is below the blocking distance.

ERR 203 Peak Lost

2

The signal peak is not found

within the measuring

window that filters the

signals received by the

antenna. The measurement

is not correct. The device

will automatically increase

this window to find the

correct signal.

Do a check of the device, tank and the

process and make sure that the data

agrees with the device configuration. If

necessary, record a new empty spectrum.

Follow the instructions on page 82. If

necessary, speak to the supplier.

Maintenance (NE 107 status signal)

-

Empty Spectrum

Invalid

5

The empty spectrum stored

in the device does not agree

with the installation. If you

change the device

configuration (tank height

etc.), this message will be

shown. The recorded empty

spectrum will not be used by

the device while this error

message is shown.

1

Record a new empty spectrum. Follow the

instructions on page 82.

_

Signal Weak

4

The signal amplitude is less

than the average value. This

can occur if the liquid is

agitated or if there is foam

in the tank. If this error

occurs frequently, the

device will possibly show

the "Peak Lost (Level Lost)"

error message.

1

If this error occurs frequently, it is possible

that you must install the device in a stilling

well or use a different antenna type.

_

Signal Strong

4

This error can occur if there

is a large change in signal

amplitude.

1

No corrective action is necessary.

_

Bad Measurement

Quality

4

The measurement is

incorrect and continues to

be incorrect after more than

10 s. This error can occur if

the tank contents are

immediately below the

antenna.

1

Record the process with the PACTware™

software tool to find the cause of the

problem. If necessary, speak to the

supplier.

_

Temperature

<-35°C / -31°F

3

The process connection or

the ambient temperaure is

less than -35°C / -31°F. This

temperature is near to the

minimum limit for device

operation.

1

Measure the ambient temperature. De-

energize the device until the ambient

temperature is back in the given range. If

the temperature does not stay in the

correct range, make sure that there is

insulation around the signal converter.

Error

code

Error Message

Status

marker

shown

Cause

Corrective action