Operation, 5 distance measurement – KROHNE OPTIWAVE 5200 C_F EN User Manual

Page 79

background image

OPERATION

6

79

OPTIWAVE 5200 C/F

www.krohne.com

07/2013 - 4001904902 - HB OPTIWAVE 5200 R02 en

How to change from multidrop to point-to-point mode

• Enter the supervisor menu.
• Push [>>>>], 5 × [

] and [>>>>] to go to menu item ADDRESS (2.6.1).

• Push [>>>>] to change the value. Enter the value 0 and push [^

^

^

^] to confirm.

• Push [^

^

^

^] to go back to the "STORE" screen.

• Push [

] or [

] to set the screen to STORE YES

STORE YES

STORE YES

STORE YES and push [^

^

^

^].

i

The output is set to point-to-point mode. The current output changes to a range of 4...20 mA
or 3.8...20.5 mA (this range is set in menu item RANGE I (2.4.2)).

6.4.5 Distance measurement

The device displays distance measurements when the output function is set to
"Distance". Menu items related to distance measurement are:

• Output Function (2.4.1)
• Tank Height (2.3.1)
• Blocking Distance (2.3.2)

For more data about the menu items, refer to

Function description

on page 68, table 2.

Supervisor menu.

CAUTION!
If the distance for 4 mA is set in the blocking distance, the device will not be able to use the full
current output range.

Figure 6-4: Distance measurement

1 Tank Height (2.3.1)
2 Blocking Distance (2.3.2)
3 4 mA Setting (2.4.3)
4 20 mA Setting (2.4.4)
5 Maximum effective measuring range
6 Non-measurement zone