6.4.2 Test

Use this procedure to test the loop current. « xx » in the illustrations shows that you can change
the value or the parameter. Push the keypad buttons in the correct sequence:

Procedure

Screen

Step

Description

Default screen.

[>>>>], [

] and [>>>>].

Enter the password: [>

>>>], [^

^

^

^], [

], [

], [>

>>>]

and [^

^

^

^].

[^

^

^

^]

[

].

[>>>>].

[>>>>].

[

] to decrease the value or [

] to

increase the value.

[^

^

^

^] to confirm.

This step sets the loop current value. Make

a selection from 3.5, 4, 6, 8, 10, 12, 14, 16,

18, 20 or 22 mA.

[^

^

^

^] 3 times to go back to the default

screen.

The loop current goes back to initial value.

Default screen.