4.3 Remote device data

4.3.1 Requirements for signal cables supplied by the customer

Non-Ex devices only:

Non-Ex devices only:

Non-Ex devices only:

Non-Ex devices only: The signal cable is an option for non-Ex devices. If the signal cable is not
supplied by the device manufacturer, the cable must have properties that follow:

Basic properties

• Twisted cable 2 by 2, shielded or screened. For example, multicore cable — reference

MCD 5123 — from Cabletec ICS/JP Electronics.

Maximum length of the signal cable

• 100 m / 328 ft

Temperature

• Use electrical cable with the applicable temperature rating for the operating conditions.
• Ambient temperature range: -40...+80°C / -40...+175°F
• We recommend that the cable agrees with UL 94V-0.

Dimensions of the insulated conductors

• Min.-max. cross-sectional area of the conductors: 4Ч0.326...4Ч2.5 mm² (22....14 AWG),

shielded cable

• Use the applicable cable for the cable glands (Ø6....10 mm / 0.24...0.39¨).
• Use the applicable cable glands for the cable entry openings in the housing.

Electrical characteristics

• Test voltage: Insulated conductor / shield (screen) ≥ 500 VAC
• Line resistance: < 55 Ω/km
• The cable must agree with EN 60811 (Low Voltage Directive) or equivalent national

regulations.

DANGER!
An Ex-approved signal cable is supplied by the manufacturer with devices for hazardous
locations. Use of this signal cable is mandatory.