OPERATION

80

OPTIWAVE 5200 C/F

www.krohne.com

07/2013 - 4001904902 - HB OPTIWAVE 5200 R02 en

6.4.6 Level measurement

The device displays level measurements when the output function is set to "Level".
Menu items related to level measurement are:

• Output Function (2.4.1)
• Tank Height (2.3.1)
• Blocking Distance (2.3.2)

For more data about the menu items, refer to

Function description

on page 68, table 2:

Supervisor menu.

CAUTION!
If the level for the 20 mA is set in the blocking distance, the device will not be able to use the full
current output range.

Figure 6-5: Level measurement

1 Tank Height (2.3.1)
2 Blocking Distance (2.3.2)
3 Maximum effective measuring range
4 20 mA Setting (2.4.4)
5 4 mA Setting (2.4.3)
6 Non-measurement zone