2.0.0 Supervisor menu
Menu
No.
Function
Function description
Selection list
Default
2.1.0 COMMISSION.
2.1.1
PARAMETERS
This starts a quick set-up procedure
applicable to most applications. The
supervisor can give the tank height (TANK
HEIGHT), type of tank (TANK TYPE), output
function (OUTPUT FUNC.), current output
range (RANGE I), 4 mA setting (SCALE 4mA),
20 mA setting (SCALE 20mA), error delay
(ERROR DELAY) and tag name (TAG NAME).
2.1.2
EMP.SPEC.REC.
Fixed and moving objects in the tank cause
interference signals. Put them through this
filter to correctly measure the tank contents.
A quick set-up procedure will go through the
steps that follow (refer also to "How to make
a filter to remove radar signal interference"
on page 82):
1
Do you have a completely filled tank?
Do you have a completely filled tank?
Do you have a completely filled tank?
Do you have a completely filled tank?
If the tank is full, it is not possible to
complete this procedure. The tank must be
partially filled or empty.
Yes [>
>>>], No [
]
2
Please, activate moving parts!
Please, activate moving parts!
Please, activate moving parts!
Please, activate moving parts!
We recommend that you switch on moving
equipment to filter all interference signals.
OK [>>>>]
3
Is your tank partially filled or empty?
Is your tank partially filled or empty?
Is your tank partially filled or empty?
Is your tank partially filled or empty?
If the tank is partially filled, the device must
include the tank contents when it filters the
signal.
Partially [>>>>], Empty [
]
4
MEAS.DISTANCE
MEAS.DISTANCE
MEAS.DISTANCE
MEAS.DISTANCE
If the tank is partially filled, type in a distance
shorter than that between the flange and the
tank contents.
min-max:
0…tank height (2.3.1)
distance to
tank contents -
300 mm / 12¨
5
Emp.Spec.Type
Emp.Spec.Type
Emp.Spec.Type
Emp.Spec.Type
Use the average value for tanks which
contain fixed objects only. Use the maximum
value for tanks which contain many objects or
moving objects.
Maximum, Average
?
6
Recording in progress
Recording in progress
Recording in progress
Recording in progress
Reading in progress
Reading in progress
Reading in progress
Reading in progress
7
Empty spectrum graph
Empty spectrum graph
Empty spectrum graph
Empty spectrum graph
This shows a set of spectra (signals found in
the tank). It also gives the amplitude and
location of each signal. Push [>>>>] to make a
selection from the available spectra.
8
Do you want to save the empty spectrum
data?
Yes [>
>>>], No [
]
2.2.0 TESTS
2.2.1
SET OUTPUT
This sets the current output to a test value
[mA]. The output will change to the given
value, independent of the measured value.
The current output will go back to the
measured value when the display goes back
to the menu level.
3.5, 4, 6, 8, 10, 12, 14,
16, 18, 20 or 22 mA
3.5 mA