2.0.0 Supervisor menu

Menu
No.

Function

Function description

Selection list

Default

2.1.0 COMMISSION.

2.1.1

PARAMETERS

This starts a quick set-up procedure

applicable to most applications. The

supervisor can give the tank height (TANK

HEIGHT), type of tank (TANK TYPE), output

function (OUTPUT FUNC.), current output

range (RANGE I), 4 mA setting (SCALE 4mA),

20 mA setting (SCALE 20mA), error delay

(ERROR DELAY) and tag name (TAG NAME).

2.1.2

EMP.SPEC.REC.

Fixed and moving objects in the tank cause

interference signals. Put them through this

filter to correctly measure the tank contents.

A quick set-up procedure will go through the

steps that follow (refer also to "How to make

a filter to remove radar signal interference"

on page 82):

1

Do you have a completely filled tank?

Do you have a completely filled tank?

Do you have a completely filled tank?

Do you have a completely filled tank?

If the tank is full, it is not possible to

complete this procedure. The tank must be

partially filled or empty.

Yes [>

>>>], No [

]

2

Please, activate moving parts!

Please, activate moving parts!

Please, activate moving parts!

Please, activate moving parts!

We recommend that you switch on moving

equipment to filter all interference signals.

OK [>>>>]

3

Is your tank partially filled or empty?

Is your tank partially filled or empty?

Is your tank partially filled or empty?

Is your tank partially filled or empty?

If the tank is partially filled, the device must

include the tank contents when it filters the

signal.

Partially [>>>>], Empty [

]

4

MEAS.DISTANCE

MEAS.DISTANCE

MEAS.DISTANCE

MEAS.DISTANCE

If the tank is partially filled, type in a distance

shorter than that between the flange and the

tank contents.

min-max:

0…tank height (2.3.1)

distance to

tank contents -

300 mm / 12¨

5

Emp.Spec.Type

Emp.Spec.Type

Emp.Spec.Type

Emp.Spec.Type

Use the average value for tanks which

contain fixed objects only. Use the maximum

value for tanks which contain many objects or

moving objects.

Maximum, Average

?

6

Recording in progress

Recording in progress

Recording in progress

Recording in progress

Reading in progress

Reading in progress

Reading in progress

Reading in progress

7

Empty spectrum graph

Empty spectrum graph

Empty spectrum graph

Empty spectrum graph

This shows a set of spectra (signals found in

the tank). It also gives the amplitude and

location of each signal. Push [>>>>] to make a

selection from the available spectra.

8

Do you want to save the empty spectrum

data?

Yes [>

>>>], No [

]

2.2.0 TESTS

2.2.1

SET OUTPUT

This sets the current output to a test value

[mA]. The output will change to the given

value, independent of the measured value.

The current output will go back to the

measured value when the display goes back

to the menu level.

3.5, 4, 6, 8, 10, 12, 14,

16, 18, 20 or 22 mA

3.5 mA