Electrical connections, 6 networks, 1 general information – KROHNE OPTIWAVE 5200 C_F EN User Manual

Page 53: 2 point-to-point connection

background image

ELECTRICAL CONNECTIONS

4

53

OPTIWAVE 5200 C/F

www.krohne.com

07/2013 - 4001904902 - HB OPTIWAVE 5200 R02 en

• Make sure that the gaskets are not damaged.
• Make sure that the electrical cables are not damaged.
• Make sure that the electrical cables agree with the national electrical code.
• The cables are in a loop in front of the device 1 so water does not go into the housing.
• Tighten the cable feedthroughs 2.
• Close unused cable feedthroughs with dummy plugs 3.

The diameter of the outer sheath of the electrical cable and must be 6…10 mm or 0.2…0.39¨.

4.6 Networks

4.6.1 General information

The device uses the HART

®

communication protocol. This protocol agrees with the HART

®

Communication Foundation standard. The device can be connected point-to-point. It can also
operate in a multi-drop network of up to 15 devices.

The device output is factory-set to communicate point-to-point. To change the communication
mode from point-to-point

point-to-point

point-to-point

point-to-point to multi-drop

multi-drop

multi-drop

multi-drop, refer to

HART

®

network configuration on page 78.

4.6.2 Point-to-point connection

Figure 4-14: Point-to-point connection (non-Ex)

1 Address of the device (0 for point-to-point connection)
2 4...20 mA + HART

®

3 Resistor for HART

®

communication

4 Power supply
5 HART

®

converter

6 HART

®

communication software