Description of hart interface, 3 connection variants, 4 hart – KROHNE OPTIWAVE 5200 C_F EN User Manual
Page 124: Device variables, 2 multi-drop connection (2-wire connection)
9
DESCRIPTION OF HART INTERFACE
124
OPTIWAVE 5200 C/F
www.krohne.com
07/2013 - 4001904902 - HB OPTIWAVE 5200 R02 en
9.3 Connection variants
The signal converter is a 2-wire device with 4...20 mA current output and HART
®
interface.
• Multi-Drop Mode is supported
Multi-Drop Mode is supported
Multi-Drop Mode is supported
Multi-Drop Mode is supported
In a Multi-Drop communication system, more than 1 device is connected to a common
transmission cable.
• Burst Mode is not supported
Burst Mode is not supported
Burst Mode is not supported
Burst Mode is not supported
There are two ways of using the HART
®
communication:
• as Point-to-Point connection and
• as Multi-Drop connection with 2-wire connection.
9.3.1 Point-to-Point connection - analogue / digital mode
Point-to-Point connection between the signal converter and the HART
®
Master.
The current output of the device is passive.
Also refer to
Point-to-point connection
on page 53.
9.3.2 Multi-Drop connection (2-wire connection)
Up to 15 devices may be installed in parallel (this signal converter and other HART
®
devices).
For an illustration of multi-drop networks, refer to
Multi-drop networks
on page 54.
For data on communication in multi-drop mode, refer to
HART
®
network configuration on page
78.
9.4 HART
®
device variables
The HART® dynamic variables PV (Primary Variable), SV (Secondary Variable), TV (Third Variable)
and 4V (Fourth Variable) can be assigned to any of the device variables.
The HART
®
dynamic variable PV is always connected to the HART
®
current output which is, for
example, assigned to level measurement.
HART
®
device variable
Code
Type
level
1
linear
distance
2
linear
conversion
3
linear
ullage conversion
4
linear
reflection
5
linear