Operation, 2 how to get access to the commissioning menu – KROHNE OPTIWAVE 5200 C_F EN User Manual
Page 63
OPERATION
6
63
OPTIWAVE 5200 C/F
www.krohne.com
07/2013 - 4001904902 - HB OPTIWAVE 5200 R02 en
6.3.2 How to get access to the commissioning menu
The commissioning menu contains the menu items that are necessary for most configurations of
the device. The menu items are divided into 2 groups: "Parameters" and "Empty Spectrum
Recording". The "Parameters" group lets the supervisor set the tank height, tank type (process,
storage, ...), output function, output current range, 4 mA output setting, 20 mA output setting,
error delay and tag name. "Empty Spectrum Recording" is a procedure that finds interference
signals in the tank and uses a filter to remove them from the measurement data.
Do the steps that follow:
• Push the [>>>>] button.
i
This shows the Information
Information
Information
Information menu. The Information
Information
Information
Information menu is read only and does not have
password security.
• Push the [
] button one time to scroll up to the Supervisor
Supervisor
Supervisor
Supervisor menu.
i
The screen shows the text "2.0.0 SUPERVISOR".
• Push the [>>>>] button one time.
i
The screen shows a line. You must enter the password. Push the buttons under the display
screen 6 times (in total and in a given order) to to get access to Configuration mode.
• Type in the password. The factory-set password is [>
>>>], [^
^
^
^], [
], [
], [>>>>] and [^
^
^
^].
i
The device shows the text "2.1.0 COMMISSION.".
• Push [>>>>]. Do the basic configuration of the device in the "'Parameters" menu. For more data on
the procedure, refer to
Quick Setup (Parameters)
on page 75. Push [^
^
^
^] at the end of each step
of the procedure to continue to the next step.
• Push [
] to go to menu item 2.1.2 EMP.SPEC.REC. Push [>
>>>] to start the empty spectrum
recording procedure. For more data, refer to
Function description
on page 68, Table 2:
Supervisor.
CAUTION!
SIL-approved devices: For data about critical device parameters for SIL approval, refer to the
Safety Manual (SIL approval).
INFORMATION!
HOW TO SET THE SUPERVISOR PASSWORD TO "ON" OR "OFF"
The supervisor password is set to "on" by default. If it is necessary to set this function to "off",
refer to Function description on page 68
, Table 2: Supervisor menu, menu item PSWD YES/NO
(2.7.4).
INFORMATION!
HOW TO CHANGE THE SUPERVISOR PASSWORD
You can change the password for the supervisor menu. For more data, refer to Function
description on page 68
, Table 2: Supervisor menu, menu item PASSWORD (2.7.5).